14 Multi CPU Errors (A) [C80]
A01

Parameter error (module)

Details
In the multiple CPU system, the I/O module or intelligent function module controlled by another CPU mod-
ule is specified in the module parameters.
Remedy
Check the detailed information (parameter information) of the error by executing module diagnostics using
the engineering tool, and correct the parameter setting corresponding to the displayed number. If the same
error code is displayed again, the possible cause is a hardware failure of the data memory in the CPU mod-
ule or the module (I/O module or intelligent function module) connected. Please consult your local Mitsub-
ishi representative.
A01
Parameter error (module)
Details
The I/O numbers set in the system parameters differ from those of the module actually mounted.
The target module is not mounted on the slot where the system parameters and module parameters are
set.
The module type set in parameter differs from that of the module actually mounted.
Remedy
Check if the system configuration displayed on the system monitor window match the actual system con-
figuration.
Check the detailed information (parameter information) of the error by executing module diagnostics using
the engineering tool, and correct the parameter setting corresponding to the displayed number. If the same
error code is displayed again, the possible cause is a hardware failure of the data memory in the CPU mod-
ule or the module (I/O module or intelligent function module) connected. Please consult your local Mitsub-
ishi representative.
A01
Parameter error (module)
Details
The intelligent function module has detected a module parameter error.
Remedy
Check the detailed information (system configuration information) of the error by executing module diag-
nostics using the engineering tool, and check the module corresponding to the displayed I/O number. If the
same error code is displayed again, the possible cause is a hardware failure of the data memory in the CPU
module or the intelligent function module connected. Please consult your local Mitsubishi representative.
A01

Parameter error (network)

Details
Network numbers are overlapping.
Remedy
Check the detailed information (parameter information) of the error by executing module diagnostics using
the engineering tool, and correct the parameter setting corresponding to the displayed number. If the same
error code is displayed again, the possible cause is a hardware failure of the data memory in the CPU mod-
ule or the intelligent function module connected. Please consult your local Mitsubishi representative.
A01
Parameter error (network)
Details
Different network types (CC IE Control extended mode/normal mode) are set between the control station
and the normal station.
Remedy
Check the detailed information (parameter information) of the error by executing module diagnostics using
the engineering tool, and correct the parameter setting corresponding to the displayed number. If the same
error code is displayed again, the possible cause is a hardware failure of the data memory in the CPU mod-
ule or the intelligent function module connected. Please consult your local Mitsubishi representative.
185
2240
2241
2242
2260
2261