Module Configuration Error; Parameter - Mitsubishi Electric M800 Series Manual

Hide thumbs Also See for M800 Series:
Table of Contents

Advertisement

M800/M80/E80/C80 Series Alarm/Parameter Manual
14 Multi CPU Errors (A) [C80]
A01

Module configuration error

Details
The number of points assigned to the intelligent function module in the system parameters ("I/O Assign-
ment Setting") is smaller than that of the module actually mounted.
Remedy
Re-set the number of points in the system parameters in accordance with the intelligent function module
actually mounted.
A01
Module configuration error
Details
Nine or more CC-Link IE Controller Network modules* are mounted in the entire system.
The CC-Link IE built-in Ethernet interface module is included if the module is used as a CC-Link IE Con-
troller Network module.
Remedy
Reduce the number of CC-Link IE Controller Network modules* to eight or less in the entire system.
The CC-Link IE built-in Ethernet interface module is included if the module is used as a CC-Link IE Con-
troller Network module.
A01
Module configuration error
Details
Two or more interrupt modules (QI60) with no interrupt pointer setting are mounted.
The interrupt pointer numbers are overlapping in the interrupt module (QI60) with no interrupt pointer set-
ting and a module with an nterrupt pointer setting.
Remedy
Mount only one QI60 in the entire system.
Configure the interrupt pointer setting for the QI60.
Correct the interrupt pointer setting.
A01
Module configuration error
Details
A module is mounted on the 65th slot or later.
Remedy
Remove the module mounted on the 65th slot or later.
A01
Module configuration error
Details
A module is mounted on the slot whose number is later than that specified in the system parameters ("I/O
Assignment Setting").
Remedy
Remove the module mounted on the slot whose number is later than that specified in the system param-
eters.
A01
Module configuration error
Details
A module is mounted over or across the maximum number of I/O points (4096).
Remedy
Remove the module mounted over or across the maximum number of I/O points (4096).
Replace the module mounted on the last slot to the one that does not exceed the maximum number of I/
O points (4096).
A01
Module configuration error
Details
There is no response from the I/O module or intelligent function module accessed.
Remedy
Check and correct the I/O assignment setting in the system parameters.
The possible cause is a hardware failure of the I/O module or intelligent function module accessed. Please
consult your local Mitsubishi representative.