A01
Module configuration error
Details
The number of points assigned to the intelligent function module in the system parameters ("I/O Assign-
ment Setting") is smaller than that of the module actually mounted.
Remedy
Re-set the number of points in the system parameters in accordance with the intelligent function module
actually mounted.
A01
Module configuration error
Details
Nine or more CC-Link IE Controller Network modules* are mounted in the entire system.
The CC-Link IE built-in Ethernet interface module is included if the module is used as a CC-Link IE Con-
troller Network module.
Remedy
Reduce the number of CC-Link IE Controller Network modules* to eight or less in the entire system.
The CC-Link IE built-in Ethernet interface module is included if the module is used as a CC-Link IE Con-
troller Network module.
A01
Module configuration error
Details
Two or more interrupt modules (QI60) with no interrupt pointer setting are mounted.
The interrupt pointer numbers are overlapping in the interrupt module (QI60) with no interrupt pointer set-
ting and a module with an nterrupt pointer setting.
Remedy
Mount only one QI60 in the entire system.
Configure the interrupt pointer setting for the QI60.
Correct the interrupt pointer setting.
A01
Module configuration error
Details
A module is mounted on the 65th slot or later.
Remedy
Remove the module mounted on the 65th slot or later.
A01
Module configuration error
Details
A module is mounted on the slot whose number is later than that specified in the system parameters ("I/O
Assignment Setting").
Remedy
Remove the module mounted on the slot whose number is later than that specified in the system param-
eters.
A01
Module configuration error
Details
A module is mounted over or across the maximum number of I/O points (4096).
Remedy
Remove the module mounted over or across the maximum number of I/O points (4096).
Replace the module mounted on the last slot to the one that does not exceed the maximum number of I/
O points (4096).
A01
Module configuration error
Details
There is no response from the I/O module or intelligent function module accessed.
Remedy
Check and correct the I/O assignment setting in the system parameters.
The possible cause is a hardware failure of the I/O module or intelligent function module accessed. Please