M800/M80/E80/C80 Series Alarm/Parameter Manual
5 System Alarms (Z)
5System Alarms (Z)
Z02

System error

Details
The operation result is illegal.
Remedy
Contact the service center.
Z11

CC-L IE F communication error

Details
A communication error has occurred in the communication that uses a CC-Link IE field network unit.
n1: Indicates the No. of slot to which the expansion unit with the communication error or diagnostic alarm is
mounted (in hexadecimal format).
n2: Indicates the alarm No. of the slot where the communication error or diagnostic alarm is occurring (in hexa-
decimal format).
Refer to the list of messages in specification manual.
Z13

CC-L IE F parameter error

Details
Parameter setting of #[Parameter No.] is incorrect.
Refer to the list of messages in specification manual.
Remedy
Correct the setting.
Z14

CC-Link IE F H/W test status

Details
H/W test is completed for the CC-Link IE field network unit.
Check the test result.
n1: Indicates the H/W test result of slot 1 (in hexadecimal format).
n2: Indicates the H/W test result of slot 2 (in hexadecimal format).
0: H/W test is normally completed or not performed
2: External self-loopback test is completed with connection error
3: External self-loopback test is completed with communication error
FFFF: H/W test is underway
Remedy
Take the following measures according to the test result.
0: Check the communication mode.
If the mode is H/W test, switch it to online, and turn OFF and ON the NC power.
If a mode other than H/W test is active, check the result of the other slot and take the measures.
2: Make sure the connection of Ethernet cable, or exchange the cable. And then perform the test again.
If the error occurs again, exchange the H/W.
3: Exchange the Ethernet cable, and perform the test again.
If the error occurs again, exchange the H/W.
FFFF: Turn OFF and ON the NC power.
If the result is unchanged, exchange the H/W.
IB-1501279-H
n1 n2
(Parameter No.)
n1 n2
82