M800/M80/E80/C80 Series Alarm/Parameter Manual
15 User Parameters
#9756

Host 3 Wrd pos: name

[M8]
Set the file name display position (nth word from left) of the list displayed when the ftp command "dir" is ex-
ecuted.
(Note) One word designates a character string divided by one or more spaces.
---Setting range---
0 to 100
0: Default value
[C80]
Not used.
#9757

Host 3 Wrd pos: size

[M8]
Set the size display position (nth word from left) of the list displayed when the ftp command "dir" is executed.
(Note) One word designates a character string divided by one or more spaces.
---Setting range---
0 to 100
0: Default value
[C80]
Not used.
#9758

Host 3 Wrd pos: Dir

[M8]
Set the <DIR> display position (nth word from left) of the list displayed when the ftp command "dir" is execut-
ed.
(Note) One word designates a character string divided by one or more spaces.
---Setting range---
0 to 100
0: Default value
[C80]
Not used.
#9759

Host 3 Wrd pos: cmnt

[M8]
Set the comment (date, time, etc.) display position (nth word from left) of the list displayed when the ftp com-
mand "dir" is executed.
(Note) One word designates a character string divided by one or more spaces.
---Setting range---
0 to 100
0: Default value
[C80]
Not used.