M800/M80/E80/C80 Series Alarm/Parameter Manual
8 Emergency Stop Alarms (EMG)
EMG
Emergency stop
Details
The "emergency stop" signal for power supply is significant (open) because the external emergency stop func-
tion for power supply is enabled.
Remedy
Cancel the "emergency stop" signal.
Check for any broken wires.
EMG
Emergency stop
[M8]
Details
The contactor shutoff test is being executed.
Remedy
The emergency stop is reset automatically after the contactor shutoff is confirmed.
If the contactor shutoff is not confirmed within 5 seconds after the "contactor shutoff test" signal has been
input, the "contactor welding detected" alarm occurs and the emergency stop status remains.
Make sure that the contactor's auxiliary b contact signal is correctly output to the device that is set in
"#1330 MC_dp1" and "#1331 MC_dp2" (Contactor weld detection device 1 and 2), and then turn the power
ON again.
[C80]
Details
The contactor shutoff test is being executed.
Safety-related I/O observation has not started, while "#51595 SIO_StartCond" is 1.
Remedy
The emergency stop is reset automatically after the contactor shutoff is confirmed.
If the contactor shutoff is not confirmed within 5 seconds after the "contactor shutoff test" signal (Y742)
has been input, the "contactor welding detected" alarm occurs and the emergency stop status remains.
Make sure that the contactor's auxiliary b contact signal is correctly output to the device that is set in
"#1330 MC_dp1", "#1331 MC_dp2", "#1339 MC_dp3" and "#1340 MC_dp4" (Contactor weld detection de-
vice 1,2,3 and 4), and then turn the power ON again.
Make sure that the safety I/O device is supplied with power, before turning ON the safety I/O observation
start request signal (ZR416/Bit1).
EMG
Emergency stop
Details
The data backup for power failure might not have been executed successfully at the previous power failure.
Remedy
If this message appears frequently, the power supply may be deteriorated. Contact the service center.