M800/M80/E80/C80 Series Alarm/Parameter Manual
6 Absolute Position Detection System Alarms (Z7*)
Z70

Abs posn param restored

Details
The data has been restored by inputting the parameters during the alarm No.0001, 0002, and 0003.
Remedy
Turn the power ON again to start the operation.
(Note) To release alarm "Z70 Abs data error", enter the parameter data output when establishing the absolute
position and turn ON the power again. For the rotary axis, however, the alarm cannot be released by
entering the parameter data.
Zero point initialization: Not required
Z70

Abs posn data lost

Details
The absolute position data has been lost. An error of the multi-rotation counter data in the detector and so on
may be the cause. (Liquid penetrates into encoder connector, etc.)
Remedy
Replace the detector and complete zero point initialization.
(Note) To release alarm "Z70 Abs data error", enter the parameter data output when establishing the absolute
position and turn ON the power again. For the rotary axis, however, the alarm cannot be released by
entering the parameter data.
Zero point initialization: Required
Servo alarm No.: (9E)etc.
Z70

Abs posn error(servo alm 25)

Details
The servo alarm No. 25 was displayed and the power was turned ON again.
Remedy
Perform zero point initialization again.
(Note) To release alarm "Z70 Abs data error", enter the parameter data output when establishing the absolute
position and turn ON the power again. For the rotary axis, however, the alarm cannot be released by
entering the parameter data.
Zero point initialization: Required
Servo alarm No.: -25
Z70

Abs posn error(servo alm E3)

Details
The servo alarm No. E3 was displayed and the power was turned ON again.
Remedy
Perform zero point initialization again.
(Note) To release alarm "Z70 Abs data error", enter the parameter data output when establishing the absolute
position and turn ON the power again. For the rotary axis, however, the alarm cannot be released by
entering the parameter data.
Zero point initialization: Required
Servo alarm No.: (E3)
Z71
AbsEncoder:Backup voltage drop
Details
Backup voltage in the absolute position detector dropped.
Remedy
Replace the battery, check the cable connections, and check the detector. Turn the power ON again and per-
form zero point initialization.
Zero point initialization: Required
Alarm reset when power is turned OFF: -(Z70-0101 is displayed after the power is turned ON again.)
Servo alarm No.: 25
0005
0080
0101
0106
0001
97
(Axis name)
(Axis name)
(Axis name)
(Axis name)
(Axis name)
IB-1501279-H