M800/M80/E80/C80 Series Alarm/Parameter Manual
16 Machine Parameters
#13107-
SP107-SP111
13111
Not used. Set to "0".
#13112
SP112 IFF
Set the current feed forward rate in OMR-FF control.
The standard setting is "10000".
Setting value of 0 is equal to "10000(100%)" setting.
Set to "0" when not using OMR-FF control.
---Setting range---
0 to 32767 (0.01%)
#13113
SP113 OPLP
Set the current command value for when the open loop control is enabled.
When "0" is set, the state will be the same as when "50" is set.
When not using, set to "0".
The open loop control is enabled when "SP018/bit1" is set to "1".
---Setting range---
0 to 999 (Short-time rated %)
#13114
SP114 MKT
Set the time required to cut off the gate when turning OFF/ON the coil switch contactor.
The value should be longer than the coil switch contactor's OFF/ON time.
The standard setting is "150".
---Setting range---
0 to 3500 (ms)
#13115
SP115 MKT2
Set the time required to limit the current immediately after the coil switch contactor ON/OFF is completed and
the gate is turned ON.
The standard setting is "250".
---Setting range---
0 to 3500 (ms)
#13116
SP116 MKIL
Set the time required to limit the current immediately after the coil switch contactor ON/OFF is completed and
the gate is turned ON.
The standard setting is "120".
---Setting range---
0 to 999 (Short-time rated %)
#13117
SP117 SETM
Set the time to detect the speed excessive error alarm.
Set the time required to the machine.
The standard setting is "12".
---Setting range---
0 to 60 (s)
(PR)
#13118
SP118 MSFT
Set the magnetic pole shift amount of IPM spindle motor.
During DC excitation of the initial setup: Set the same value displayed in the "AFLT gain" on the NC monitor
screen in SP225/bit4=1.
When not using, set to "0".
---Setting range---
-18000 to 18000 (electrical angle 0.01°)
#13119
SP119
Not used. Set to "0".
#13120
SP120
Not used. Set to "0".
OMR-FF current feed forward gain
Current command value for open loop
Coil changeover gate cutoff timer
Coil changeover current limit timer
Coil changeover current limit value
Excessive speed deviation timer
Magnetic pole shift amount
607