The input of this GOOSE block must be linked either in SMT by means
of a cross or in ACT by means of a GOOSE connection (if easy
GOOSE engineering is enabled) to receive the double point values.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Functionality
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via
GOOSE.
Function block
GOOSEINTRCV
BLOCK
^INTOUT
^SRCINTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-2-en.vsd
IEC10000250 V2 EN-US
Figure 257:
GOOSEINTRCV function block
Signals
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These connections are
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
ANSI/IEEE C37.2
device number
-
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1