Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
14.6.5
Table 229:
SINGLECMD Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Steady
Pulsed
14.6.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of 13
characters in PCM600.
The output signals can be of the types Disabled, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole function
block. The length of the output pulses are 100 ms. In steady mode, SINGLECMD
function has a memory to remember the output values at power interruption of the IED.
Also a BLOCK input is available used to block the updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
Description
Single command output 14
Single command output 15
Single command output 16
Default
Description
Disabled
Operation Disabled/Enabled
Section 14
Control
PID-6189-SETTINGS v6
M12447-3 v3
399