Table 671:
IRIG-B Non group settings (basic)
Name
Values (Range)
SynchType
BNC
Opto
TimeDomain
LocalTime
UTC
Encoding
IRIG-B
1344
1344TZ
TimeZoneAs1344
MinusTZ
PlusTZ
Phasor measurement unit RES670 2.2 ANSI
Technical manual
optical pulse-width modulated signal (IRIG-B 00X). The IRIG-B module is mounted
as a mezzanine card on the Analog digital conversion module (ADM).
ST
Y2
T
IEC06000304 V2 EN-US
Figure 324:
IRIG-B PC-MIP board with top left ST connector for optical IRIG-B 00X
820 nm multimode fibre optic signal input and lower left BNC connector
for IRIG-B signal input

Settings

Unit
Step
-
-
-
-
-
-
-
-
Default
Description
Opto
Type of synchronization
LocalTime
Time domain
IRIG-B
Type of encoding
PlusTZ
Time zone as in 1344 standard
Section 23
IED hardware
IEC06000304=1=en=Original.ai
PID-5187-SETTINGS v5