ABB RES670 Technical Manual page 413

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
CNDX =[ b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14 ]
b0=
BFI_3P (general pickup)
b1=
FW (forward)
b2=
REV (reverse)
b3=
BFI_A (pickup A)
b4=
FW_A (forward A)
b5=
REV_A (reverse A)
b6=
BFI_B (pickup B)
b7=
FW_B (forward B)
b8=
REV_B (reverse B)
b9=
BFI_C (pickup C)
b10=
FW_C (forward C)
b11=
REV_C (reverse C)
b12=
BFI_N (pickup N)
b13=
FW_N (forward N)
b14=
REV_N (reverse N)
The indications for common start BFI_3P, and phase-wise starts BFI_A, BFI_B and
BFI_C and neutral STN and common directional forward FW and reverse REV are all
available as outputs on the trip function.
All start and directional outputs are mapped to the IEC 61850 logical node data model
of the trip function. The time stamping is updated each time a trip or pickup signal is
changed:
The common CND output (general) is mapped as:
dirGeneral
0
unknown
1
forward
2
backward (reverse)
3
both
The phase wise directional outputs (DIR_A, DIR_B, DIR_C and DIR_N) are
mapped as:
dirPhsA, dirPhsB, dirPhsC, dirNeut
0
unknown
1
forward
2
backward (reverse)
Section 15
Logic
407