Functionality

The circuit breaker condition monitoring function (SSCBR) is used to monitor
different parameters of the breaker condition. The breaker requires maintenance when
the number of operations reaches a predefined value. For a proper functioning of the
circuit breaker, it is essential to monitor the circuit breaker operation, spring charge
indication or breaker wear, travel time, number of operation cycles and estimate the
accumulated energy during arcing periods.
Function block
SSCBR
I3P*
OPENPOS
BLOCK
CLOSEPOS
BLKALM
INVDPOS
TRIND
TRCMD
POSOPEN
TRVTOPAL
POSCLOSE
TRVTCLAL
PRESALM
OPERALM
PRESLO
OPERLO
SPRCHRST
CBLIFEAL
SPRCHRD
MONALM
RSTCBWR
IPOWALPH
RSTTRVT
IPOWLOPH
RSTIPOW
SPCHALM
RSTSPCHT
GPRESALM
GPRESLO
ANSI14000061-1-en.vsd
ANSI14000061 V1 EN-US
Figure 206:
SSCBR function block
Signals
Table 409:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKALM
BOOLEAN
TRIND
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
PRESALM
BOOLEAN
PRESLO
BOOLEAN
SPRCHRST
BOOLEAN
SPRCHRD
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for current input
0
Block all the alarm and lockout indication
0
Block all the alarms
0
Trip command from trip circuit
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Pressure alarm indication from CB
0
Pressure lockout indication from CB
0
CB spring charging started indication signal
0
CB spring charged indication signal
Section 16
Monitoring
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v11
GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11