Function Block - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 15
Logic
15.1.3
15.1.4
402

Function block

SMPPTRC (94)
BLOCK
TRIP
BLKLKOUT
TR_A
TRINP_3P
TR_B
TRINP_A
TR_C
TRINP_B
TR1P
TRINP_C
TR2P
PS_A
TR3P
PS_B
CLLKOU T
PS_C
BFI_3P
1PTRZ
BFI_A
1PTRGF
BFI_B
P3PTR
BFI_C
SETLKOUT
STN
RSTLKOUT
FW
CND
REV
ANSI05000707-4-en.vsdx
ANSI05000707 V4 EN-US
Figure 142:
SMPPTRC (94) function block
Signals
Table 230:
SMPPTRC Input signals
Name
Type
BLOCK
BOOLEAN
BLKLKOUT
BOOLEAN
TRIN
BOOLEAN
TRINL1
BOOLEAN
TRINL2
BOOLEAN
TRINL3
BOOLEAN
PSL1
BOOLEAN
PSL2
BOOLEAN
PSL3
BOOLEAN
1PTRZ
BOOLEAN
1PTREF
BOOLEAN
P3PTR
BOOLEAN
SETLKOUT
BOOLEAN
RSTLKOUT
BOOLEAN
STDIR
INTEGER
Default
Description
0
Block of function
0
Blocks circuit breaker lockout output (CLLKOUT)
0
Trip all phases
0
Trip phase L1
0
Trip phase L2
0
Trip phase L3
0
Functional input for phase selection in phase L1
0
Functional input for phase selection in phase L2
0
Functional input for phase selection in phase L3
0
Input for phase selective carrier aided trip
0
Input for phase selective earth fault trip
0
Prepare all tripping to be three-phase
0
Input for setting the circuit breaker lockout function
0
Input for resetting the circuit breaker lockout function
0
General start direction input
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
M12638-3 v7
GUID-2918ECA6-4D98-493F-A33C-2D33DE64AE3B v1