Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 11
Multipurpose protection
11.1.4
Table 185:
CVGAPC Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CurrentInput
Phase A
Phase B
Phase C
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
VoltageInput
Phase A
Phase B
Phase C
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
OperHarmRestr
Disabled
Enabled
l_2nd/l_fund
10.0 - 50.0
BlkLevel2nd
10 - 5000
EnRestrainCurr
Disabled
Enabled
RestrCurrInput
PosSeq
NegSeq
3*ZeroSeq
Max
RestrCurrCoeff
0.00 - 5.00
RCADir
-180 - 180
ROADir
1 - 90
Table continues on next page
328

Settings

Unit
Step
-
-
-
-
-
-
-
-
%
1.0
%IB
1
-
-
-
-
-
0.01
Deg
1
Deg
1
Default
Description
Disabled
Operation Disabled/Enabled
MaxPh
Select current signal which will be measured
inside function
MaxPh
Select voltage signal which will be measured
inside function
Disabled
Disable/Enable operation of 2nd harmonic
restrain
20.0
Ratio of second to fundamental current
harmonic in %
5000
Harm analyse disabled above this current
level in % of fundamental current
Disabled
Disable/Enable current restrain function
PosSeq
Select current signal which will be used for
current restrain
0.00
Restraining current coefficient
-75
Relay Characteristic Angle
75
Relay Operate Angle
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3857-SETTINGS v9
Technical manual