8.1.5
Table 93:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
AngleRCA
40 - 65
AngleROA
40 - 89
NumPhSel
1 out of 3
2 out of 3
3 out of 3
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Pickup1
5 - 2500
t1
0.000 - 60.000
TD1
0.05 - 999.00
IMin1
1 - 10000
t1Min
0.000 - 60.000
MultPU1
1.0 - 10.0
DirModeSel2
Disabled
Non-directional
Forward
Reverse
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Settings

Unit
Step
-
-
Deg
1
Deg
1
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
s
0.001
-
0.1
-
-
Default
Description
Disabled
Operation Disabled/Enabled
55
Relay characteristic angle (RCA)
80
Relay operation angle (ROA)
1 out of 3
Number of phases required for phase
selection (1 of 3, 2 of 3, 3 of 3)
Non-directional
Directional mode of step 1 (Disabled, Nondir,
Forward, Reverse)
ANSI Def. Time
Selection of time delay curve type for step 1
1000
Operating phase current level for step 1 in %
of IBase
0.000
Def time delay or add time delay for inverse
char of step 1
0.05
Time dial multiplier for the inverse time delay
for step 1
100
Minimum operate current for step1 in % of
IBase
0.000
Minimum operate time for inverse curves for
step 1
2.0
Multiplier for current operate level for step 1
Non-directional
Directional mode of step 2 (Disabled, Nondir,
Forward, Reverse)
Section 8
Current protection
PID-6973-SETTINGS v3