Gas Medium Supervision Ssimg (63) - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 16
Monitoring
16.2
16.2.1
524
Table 396:
CMSQI technical data
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Table 397:
VMSQItechnical data
Function
Voltage positive sequence, V1
Voltage zero sequence, 3V0
Voltage negative sequence, V2
Phase angle
Table 398:
VNMMXU technical data
Function
Voltage
Phase angle

Gas medium supervision SSIMG (63)

Identification
Function description
Insulation gas monitoring function
Range or value
(0.1–4.0) × I
n
(0.1–1.0) × I
n
(0.1–1.0) × I
n
(0.1–4.0) × I
n
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
Range or value
(5 to 175) V
(5 to 175) V
IEC 61850
IEC 60617
identification
identification
SSIMG
-
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5
Accuracy
±0.3% of I
at I ≤ 0.5 × I
n
n
±0.3% of I at I > 0.5 × I
n
±0.3% of I
at I ≤ 0.5 × I
n
n
±0.3% of I at I > 0.5 × I
n
±0.3% of I
at I ≤ 0.5 × I
n
n
±0.3% of I at I > 0.5 × I
n
±1.0 degrees at 0.1 × I
< I ≤ 0.5 ×
n
I
n
±0.5 degrees at 0.5 × I
< I ≤ 4.0 ×
n
I
n
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Accuracy
±0.5% of V at V ≤ 50 V
±0.2% of V at V > 50 V
±0.5% of V at V ≤ 50 V
±0.2% of V at V > 50 V
±0.5% of V at V ≤ 50 V
±0.2% of V at V > 50 V
±0.5 degrees at V ≤ 50 V
±0.2 degrees at V > 50 V
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
Accuracy
±0.5% of V at V ≤ 50 V
±0.2% of V at V > 50 V
±0.5° at V ≤ 50 V
±0.2° at V > 50 V
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
ANSI/IEEE C37.2
device number
63
Technical manual