Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
19.7.2.5
Table 506:
I103MEAS Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
MaxIa
1 - 99999
MaxIb
1 - 99999
MaxIc
1 - 99999
MaxIN
1 - 99999
MaxVa
0.05 - 2000.00
MaxVb
0.05 - 2000.00
MaxVc
0.05 - 2000.00
MaxVab
0.05 - 2000.00
MaxVn
0.05 - 2000.00
MaxP
0.00 - 2000.00
MaxQ
0.00 - 2000.00
MaxF
15.0 - 66.0
19.7.3
19.7.3.1
19.7.3.2
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Settings

Unit
Step
-
1
A
1
A
1
A
1
A
1
kV
0.05
kV
0.05
kV
0.05
kV
0.05
kV
0.05
MW
0.05
MVAr
0.05
Hz
1.0
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR
Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each block in
the private range, and the Information number parameter for each block.
Identification
Function description
Measurands user defined signals for
IEC 60870-5-103
Station communication
Default
Description
1
Function type (1-255)
3000
Maximum current phase A
3000
Maximum current phase B
3000
Maximum current phase C
3000
Maximum residual current IN
230.00
Maximum voltage for phase A
230.00
Maximum voltage for phase B
230.00
Maximum voltage for phase C
400.00
Maximum voltage for phase-phase AB
230.00
Maximum residual voltage VN
1200.00
Maximum value for active power
1200.00
Maximum value for reactive power
51.0
Maximum system frequency
Function block
IEC 60617
name
identification
I103MEASUSR
-
Section 19
PID-6625-SETTINGS v4
GUID-FC9ED4BD-F11C-4BDA-8CDB-3ACF00931D3A v1
GUID-A9E21066-354B-453D-8D9B-E86EE31CF5F9 v1
ANSI/IEEE C37.2
device number
-
687