1MRK 511 408-UUS A
Name
Values (Range)
RatedOperCurr
100.00 - 5000.00
OperNoRated
1 - 99999
RatedFltCurr
500.00 - 99999.99
OperNoFault
1 - 10000
tTrOpenAlm
0.000 - 0.200
tTrCloseAlm
0.000 - 0.200
OperAlmLevel
0 - 9999
OperLOLevel
0 - 9999
AccSelCal
Aux Contact
Trip Signal
CurrExponent
0.50 - 3.00
AccStopCurr
5.00 - 100.00
AlmAccCurrPwr
0.00 - 20000.00
LOAccCurrPwr
0.00 - 20000.00
SpChAlmTime
0.00 - 60.00
InitCBRemLife
1 - 99999
InactiveAlDays
0 - 9999
Table 412:
SSCBR Non group settings (advanced)
Name
Values (Range)
OpenTimeCorr
-0.100 - 0.100
CloseTimeCorr
-0.100 - 0.100
DirCoef
-3.00 - -0.50
CBLifeAlmLevel
1 - 99999
ContTrCorr
-0.010 - 0.010
OperTimeDelay
0.000 - 0.200
tDGasPresAlm
0.00 - 60.00
tDGasPresLO
0.00 - 60.00
InitCounterVal
0 - 9999
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
A
0.01
1000.00
-
1
10000
A
0.01
5000.00
-
1
1000
s
0.001
0.040
s
0.001
0.040
-
1
200
-
1
300
-
-
Trip Signal
-
0.01
2.00
%IB
0.01
10.00
-
0.01
2500.00
-
0.01
2500.00
s
0.01
1.00
-
1
10000
Day
1
2000
Unit
Step
Default
s
0.001
0.010
s
0.001
0.010
-
0.01
-1.50
-
1
5000
s
0.001
0.005
s
0.001
0.020
s
0.01
0.10
s
0.01
0.10
-
1
0
Section 16
Monitoring
Description
Rated operating current of the breaker
Number of operations possible at rated
current
Rated fault current of the breaker
Number of operations possible at rated fault
current
Alarm level for open travel time
Alarm level for close travel time
Alarm level for number of operations
Lockout level for number of operations
Accumulated energy calculation selection
Current exponent value used for energy
calculation
RMS current level below which energy
accumulation stops
Alarm level for accumulated I^CurrExponent
integrated over CB open travel time
Lockout level for accumulated
I^CurrExponent integrated over CB open
travel time
Alarm level for spring charging time
Initial value for remaining life estimates
Alarm level for inactive days counter
Description
Correction for open travel time
Correction for close travel time
Directional coefficient for CB life calculation
Alarm level for CB remaining life
Correction for time difference in auxiliary and
main contacts open time
Time delay between change of status of trip
output and start of main contact separation
Time delay for gas pressure alarm
Time delay for gas pressure lockout
Initial value for number of operations
535