Impedance protection
7.1.7
7.2
7.2.1
7.2.2
154

Technical data

Table 82:
ZMRPSB (68) technical data
Function
Reactive reach
Resistive reach
Power swing detection trip time
Second swing reclaim trip time
Minimum trip current
Out-of-step protection OOSPPAM (78)
Identification
Function description
Out-of-step protection
Functionality
The out-of-step protection (OOSPPAM (78)) function in the IED can be used for both
generator protection and as well for line protection applications.
The main purpose of the OOSPPAM (78) function is to detect, evaluate, and take the
required action during pole slipping occurrences in the power system.
The OOSPPAM (78) function detects pole slip conditions and trips the generator as fast
as possible, after the first pole-slip if the center of oscillation is found to be in zone 1,
which normally includes the generator and its step-up power transformer. If the center
of oscillation is found to be further out in the power system, in zone 2, more than one
pole-slip is usually allowed before the generator-transformer unit is disconnected. A
parameter setting is available to take into account the circuit breaker opening time. If
Range or value
(0.10-3000.00) W/phase
(0.10–1000.00) W/loop
(0.000-60.000) s
(0.000-60.000) s
(5-30)% of IBase
IEC 61850
IEC 60617
identification
identification
OOSPPAM
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
M16036-1 v10
Accuracy
±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: at 0 degrees and 85
degrees
±0.2% or ±10 ms whichever is
greater
±0.2% or ±20 ms whichever is
greater
±1.0% of I
n
GUID-667DAF85-B87B-47AA-9EAA-CD349E66F22F v3
GUID-BF2F1533-BA39-48F0-A55C-0B13A393F780 v2
ANSI/IEEE C37.2
device number
78
<
GUID-BF2F7D4C-F579-4EBD-9AFC-7C03296BD5D4 v8
Technical manual