ABB RES670 Technical Manual page 183

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
tBCrv2
0.00 - 20.00
tCCrv2
0.1 - 10.0
tPRCrv2
0.005 - 3.000
tTRCrv2
0.005 - 100.000
tCRCrv2
0.1 - 10.0
HarmBlock2
Disabled
Enabled
I3>Min
5 - 2500
I3>Max
5 - 2500
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
tReset3
0.000 - 60.000
tPCrv3
0.005 - 3.000
tACrv3
0.005 - 200.000
tBCrv3
0.00 - 20.00
tCCrv3
0.1 - 10.0
tPRCrv3
0.005 - 3.000
tTRCrv3
0.005 - 100.000
tCRCrv3
0.1 - 10.0
HarmBlock3
Disabled
Enabled
I4>Min
5 - 2500
I4>Max
5 - 2500
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Disabled
%IB
1
5
%IB
1
2500
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Disabled
%IB
1
5
%IB
1
2500
Current protection
Description
Parameter B for customer programmable
curve for step 2
Parameter C for customer programmable
curve for step 2
Parameter PR for customer programmable
curve for step 2
Parameter TR for customer programmable
curve for step 2
Parameter CR for customer programmable
curve for step 2
Enable block of step 2 for harmonic restraint
Minimum used operating phase current level
for step 3 in % of IBase, if I3> is less than
I3>Min then I3> is set to I3>Min
Maximum used operating phase current level
for step 3 in % of IBase, if I3> is greater than
I3>Max then I3> is set to I3>Max
Selection of reset curve type for step 3
Constant reset time for step 3
Parameter P for customer programmable
curve for step 3
Parameter A for customer programmable
curve for step 3
Parameter B for customer programmable
curve for step 3
Parameter C for customer programmable
curve for step 3
Parameter PR for customer programmable
curve for step 3
Parameter TR for customer programmable
curve for step 3
Parameter CR for customer programmable
curve for step 3
Enable block of step 3 for harmonic restraint
Minimum used operating phase current level
for step 4 in % of IBase, if I4> is less than
I4>Min then I4> is set to I4>Min
Maximum used operating phase current level
for step 4 in % of IBase, if I4> is greater than
I4>Max then I4> is set to I4>Max