Section 16
Monitoring
16.9.5
16.9.6
Table 436:
L4UFCNT Group settings (basic)
Name
Values (Range)
Operation
Disabled
On
CountType
Positive edge
Negative edge
Both edges
CounterLimit1
1 - 65535
CounterLimit2
1 - 65535
CounterLimit3
1 - 65535
CounterLimit4
1 - 65535
MaxValue
1 - 65535
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
InitialValue
0 - 65535
588

Signals

Table 434:
L4UFCNT Input signals
Name
Type
BLOCK
BOOLEAN
INPUT
BOOLEAN
RESET
BOOLEAN
Table 435:
L4UFCNT Output signals
Name
Type
ERROR
BOOLEAN
OVERFLOW
BOOLEAN
LIMIT1
BOOLEAN
LIMIT2
BOOLEAN
LIMIT3
BOOLEAN
LIMIT4
BOOLEAN
VALUE
INTEGER
Settings
Unit
Step
-
-
-
-
-
1
-
1
-
1
-
1
-
1
-
-
-
1
Default
Description
0
Block of function
0
Input for counter
0
Reset of function
Description
Error indication on counter limit and/or initial value
settings
Overflow indication on count of greater than MaxValue
Counted value is larger than or equal to CounterLimit1
Counted value is larger than or equal to CounterLimit2
Counted value is larger than or equal to CounterLimit3
Counted value is larger than or equal to CounterLimit4
Counted value
Default
Description
Disabled
Operation Disabled/Enabled
Positive edge
Select counting on positive and/or negative
sides
100
Value of the first limit
200
Value of the second limit
300
Value of the third limit
400
Value of the fourth limit
500
Maximum count value
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
0
Initial count value after reset of the function
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6966-INPUTSIGNALS v2
PID-6966-OUTPUTSIGNALS v2
PID-6966-SETTINGS v2
Technical manual