Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 22
Basic IED functions
22.3.4
Table 602:
TESTMODE Non group settings (basic)
Name
Values (Range)
IEDTestMode
Disabled
Enabled
EventDisable
Disabled
Enabled
BlockAllFunc
Disabled
Enabled
CmdTestEd1
Disabled
Enabled
22.3.5
778

Settings

Unit
Step
-
-
-
-
-
-
-
-
Operation principle
Set the IED in test mode by
configuration, activating the input SIGNAL on the function block TESTMODE.
setting TestMode to Enabled in the local HMI, under Main menu/TEST/IED test
mode.
While the IED is in test mode, the output ACTIVE of the function block TESTMODE
is activated. The other outputs of the function block TESTMODE shows the cause of
the "Test mode: Enabled" state — input from configuration (OUTPUT signal is
activated) or setting from local HMI (SETTING signal is activated).
While the IED is in test mode, the yellow Pickup LED will flash and all functions can
be blocked depending on the configuration of the testmode component. Any function
can be unblocked individually regarding functionality and event signalling.
The deblocking is reseted when exiting test mode.
The blocking of a function concerns all output signals from the actual function, so no
outputs will be activated.
If the IED is restarted while set to IED TESTMODE by a binary input
all functions will be temporarily unblocked during startup, which might
cause unwanted operations.
The TESTMODE function block might be used to automatically block functions when
a test handle is inserted in a test switch. A contact in the test switch (RTXP24 contact
29-30) or an FT switch finger can supply a binary input which in turn is configured to
the TESTMODE function block.
Default
Description
Disabled
Activate IED Test mode
Disabled
Event disable during test mode
Enabled
Block all functions when entering IED test
mode
Disabled
Require test bit in command at test mode
(only for IEC61850 Ed1)
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
IP11343-1 v2
PID-6730-SETTINGS v1
IP12116-1 v4
M12015-4 v10
M11828-3 v8
Technical manual

Advertisement

Table of Contents
loading

Table of Contents