1MRK 511 408-UUS A
8.1.7
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
IA
REAL
IB
REAL
IC
REAL

Operation principle

Directional phase overcurrent protection, four steps OC4PTOC (51_67) is divided into
four different sub-functions. For each step x , where x is step 1, 2, 3 and 4, an operation
mode is set by DirModeSelx: Disable/Non-directional/Forward/Reverse.
The protection design can be divided into four parts:
The direction element
The harmonic restraint blocking function
The four step overcurrent function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.
Values (Range)
Unit
-
A
-
A
-
A
Section 8
Current protection
Description
Current in phase A
Current in phase B
Current in phase C
M12883-3 v10