Type
IA
REAL
IB
REAL
IC
REAL
Operation principle
Directional phase overcurrent protection, four steps OC4PTOC (51_67) is divided into
four different sub-functions. For each step x , where x is step 1, 2, 3 and 4, an operation
mode is set by DirModeSelx: Disable/Non-directional/Forward/Reverse.
The protection design can be divided into four parts:
•
The direction element
•
The harmonic restraint blocking function
•
The four step overcurrent function
•
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.
Values (Range)
Unit
-
A
-
A
-
A
Section 8
Current protection
Description
Current in phase A
Current in phase B
Current in phase C
M12883-3 v10