Monitored Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
EARPrestVal
0.000 -
100000000.000
ERFPresetVal
0.000 -
100000000.000
ERRPresetVal
0.000 -
100000000.000
17.2.6
17.2.7
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
MWh
0.001
MVArh
0.001
MVArh
0.001

Monitored data

Table 452:
ETPMMTR Monitored data
Name
Type
EAFACC
REAL
EARACC
REAL
ERFACC
REAL
ERRACC
REAL
MAXPAFD
REAL
MAXPARD
REAL
MAXPRFD
REAL
MAXPRRD
REAL
Operation principle
The instantaneous output values of active and reactive power from the Measurements
function CVMMXN are used and integrated over a selected time tEnergy to measure
the integrated energy. Figure
calculation and demand handling function ETPMMTR.
Default
Description
0.000
Preset Initial value for reverse active energy
0.000
Preset Initial value for forward reactive energy
0.000
Preset Initial value for reverse reactive energy
Values (Range)
Unit
-
MWh
-
MWh
-
MVArh
-
MVArh
-
MW
-
MW
-
MVAr
-
MVAr
240
shows the overall functionality of the energy
Section 17
Metering
PID-6872-MONITOREDDATA v3
Description
Accumulated forward active
energy value
Accumulated reverse active
energy value
Accumulated forward reactive
energy value
Accumulated reverse reactive
energy value
Maximum forward active
power demand value for set
interval
Maximum reverse active
power demand value for set
interval
Maximum forward reactive
power demand value for set
interval
Maximum reverse reactive
power demand value for set
interval
GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v3
603

Advertisement

Table of Contents
loading

Table of Contents