Values (Range)
VABAngDbRepInt
1 - 100000
VBC_DbRepInt
1 - 100000
VBC_ZeroDb
0 - 100000
VBC_Min
0.0 - 200.0
VBC_Max
0.0 - 200.0
VBC_RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
VBCAngDbRepInt
1 - 100000
VCA_DbRepInt
1 - 100000
VCA_ZeroDb
0 - 100000
VCA_Min
0.0 - 200.0
VCA_Max
0.0 - 200.0
VCA_RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
VCAAngDbRepInt
1 - 100000
Table 380:
VMMXU Non group settings (advanced)
Name
Values (Range)
VAB_HiHiLim
0.0 - 200.0
VAB_HiLim
0.0 - 200.0
VAB_LowLim
0.0 - 200.0
VAB_LowLowLim
0.0 - 200.0
VMagComp100
-10.000 - 10.000
VAB_LimHys
0.000 - 100.000
VBC_HiHiLim
0.0 - 200.0
VBC_HiLim
0.0 - 200.0
VBC_LowLim
0.0 - 200.0
VBC_LowLowLim
0.0 - 200.0
Table continues on next page
502
Unit
Step
Default
s
1
10
Type
1
10
m%
500
1000
%VB
0.1
50.0
%VB
0.1
200.0
-
-
Cyclic
s
1
10
Type
1
10
m%
500
1000
%VB
0.1
50.0
%VB
0.1
200.0
-
-
Cyclic
s
1
10
Unit
Step
Default
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%
0.001
0.000
%
0.001
5.000
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
1MRK 511 408-UUS A
Description
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of VBase
Maximum value in % of VBase
Reporting type
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of VBase
Maximum value in % of VBase
Reporting type
Cyclic report interval (s)
Description
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Magnitude factor to calibrate voltage at 100%
of Vn
Hysteresis value in % of range, common for
all limits
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase