Section 8
Current protection
Table 117:
SDEPSDE (67N) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
Table 118:
SDEPSDE (67N) Non group settings (advanced)
Name
Values (Range)
RotResV
0 deg
180 deg
8.4.6
8.4.7
8.4.7.1
234
Unit
Step
-
1
Unit
Step
-
-

Monitored data

Table 119:
SDEPSDE (67N) Monitored data
Name
Type
INCOSPHI
REAL
IN
REAL
VN
REAL
SN
REAL
ANG FI-RCA
REAL
Operation principle
Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P
and V3P containing phasors of residual current and voltage which are taken from pre-
processor blocks.
The sensitive directional ground fault protection has the following sub-functions
included:
Directional residual current protection measuring 3I
φ is defined as the angle between the residual current 3I
φ=ang(3I
)-ang(V
)|). The reference voltage (Vref) is the polarizing quantity which is
0
ref
Default
Description
1
Global base selection for function groups
Default
Description
180 deg
Setting for rotating polarizing quantity if
necessary
Values (Range)
Unit
-
A
-
A
-
kV
-
MVA
-
deg
0
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3892-MONITOREDDATA v6
Description
Magnitude of residual current
along the polarizing quantity
3I0cos(Fi-RCA)
Measured magnitude of the
residual current 3I0
Measured magnitude of the
residual voltage 3V0
Measured magnitude of
residual power 3I03V0cos(Fi-
RCA)
Angle between 3V0 and 3I0
minus RCA (Fi-RCA)
SEMOD171963-4 v5
·cos φ
0
SEMOD171963-8 v7
and the reference voltage (|
Technical manual