Section 15
Logic
15.7.9.3
Table 286:
TIMERSET Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
t
0.000 - 90000.000
15.7.9.4
15.7.10
442
Table 285:
TIMERSET Output signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN

Settings

Unit
Step
-
-
s
0.001
Technical data
Table 287:
Number of TIMERSET instances
Logic block
Quantity with cycle time
3 ms
TIMERSET
15
Exclusive OR function block XOR
The exclusive OR function (XOR) is used to generate combinatory expressions with
boolean variables. XOR has two inputs and two outputs. One of the outputs is inverted.
The output signal OUT is 1 if the input signals are different and 0 if they are the same.
Table 288:
Truth table for XOR function block
INPUT1
INPUT2
OUT
0
0
0
1
1
0
1
1
Description
Output from timer, pickup delay
Output from timer, dropout delay
Default
Disabled
0.000
Range or Value
8 ms
100 ms
15
30
(0.000–90000.000) s
NOUT
0
1
1
0
1
0
0
1
1MRK 511 408-UUS A
Description
Operation Disabled/Enabled
Delay for settable timer n
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
Accuracy
±0.5% ±10 ms
Phasor measurement unit RES670 2.2 ANSI
Technical manual
PID-6976-OUTPUTSIGNALS v1
PID-6976-SETTINGS v1
IP11018-1 v2
M11477-3 v4