Reporting - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.9.3.2
16.9.4
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Overflow indication
Actual value
...
Max value -1
Counted value
...
Max value -1
IEC12000626 V1 EN-US
Figure 232:
Overflow indication when OnMaxValue is set to rollover pulsed
The Error output is activated as an indicator of setting the counter limits and/or initial
value setting(s) greater than the maximum value. The counter stops counting the input
and all the outputs except the error output remains at zero state. The error condition
remains until the correct settings for counter limits and/or initial value setting(s) are
applied.
The function can be blocked through a block input. During the block time, input is not
counted and outputs remain in their previous states. However, the counter can be
initialized after reset of the function. In this case the outputs remain in their initial
states until the release of the block input.

Reporting

The content of the counter can be read on the local HMI.
Reset of the counter can be performed from the local HMI or via a binary input.
Reading of content and resetting of the function can also be performed remotely, for
example from a IEC 61850 client. The value can also be presented as a measurement
on the local HMI graphical display.
Function block
L4UFCNT
BLOCK
ERROR
INPUT
OVERFLOW
RESET
LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE
IEC12000029-1-en.vsd
IEC12000029 V1 EN-US
Figure 233:
L4UFCNT function block
®
®
Max value
Max value +1
®
®
Max value
Section 16
Monitoring
®
®
Max value +2
®
®
0
1
IEC12000626_1_en.vsd
GUID-7DF874A7-F7DA-48DD-8760-5E4CF05FD870 v1
GUID-C90E7375-F3CC-414A-93FC-9AC4A9156FFC v1
Max value +3
...
...
2
587