1MRK 511 408-UUS A
16.6.5
Table 421:
DRPRDRE Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PreFaultRecT
0.05 - 9.90
PostFaultRecT
0.1 - 10.0
TimeLimit
0.5 - 10.0
PostRetrig
Disabled
Enabled
MaxNoStoreRec
10 - 100
ZeroAngleRef
1 - 30
OpModeTest
Disabled
Enabled
SetInfoInDRep
Disable
Enable
Phasor measurement unit RES670 2.2 ANSI
Technical manual
B2RBDR to B22RBDR functions have the same input signal specifications as
B1RBDR but with different numbering:
B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32)
B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48)
B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64)
B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80)
B6RBDR: INPUT81 to INPUT96 (binary channels 81 to 96)
B7RBDR: INPUT97 to INPUT112 (binary channels 97 to 112)
B8RBDR: INPUT113 to INPUT128 (binary channels 113 to 128)
B9RBDR: INPUT129 to INPUT144 (binary channels 129 to 144)
B10RBDR: INPUT145 to INPUT160 (binary channels 145 to 160)
B11RBDR: INPUT161 to INPUT176 (binary channels 161 to 176)
B12RBDR: INPUT177 to INPUT192 (binary channels 177 to 192)
B13RBDR: INPUT193 to INPUT208 (binary channels 193 to 208)
B14RBDR: INPUT209 to INPUT224 (binary channels 209 to 224)
B15RBDR: INPUT225 to INPUT240 (binary channels 225 to 240)
B16RBDR: INPUT241 to INPUT256 (binary channels 241 to 256)
B17RBDR: INPUT257 to INPUT272 (binary channels 257 to 272)
B18RBDR: INPUT273 to INPUT288 (binary channels 273 to 288)
B19RBDR: INPUT289 to INPUT304 (binary channels 289 to 304)
B20RBDR: INPUT305 to INPUT320 (binary channels 305 to 320)
B21RBDR: INPUT321 to INPUT336 (binary channels 321 to 336)
B22RBDR: INPUT337 to INPUT352 (binary channels 337 to 352)

Settings

Unit
Step
-
-
s
0.01
s
0.1
s
0.1
-
-
-
1
Ch
1
-
-
-
-
Default
Description
Disabled
Operation Disabled/Enabled
0.10
Pre-fault recording time
0.5
Post-fault recording time
1.0
Fault recording time limit
Disabled
Post-fault retrig enabled (On) or not (Off)
100
Maximum number of stored disturbances
1
Trip value recorder, phasor reference channel
Disabled
Operation mode during test mode
Enable
Enable Disturbance report settings
functionality
Section 16
Monitoring
GUID-D3A8067F-80F8-4174-BD2D-4C43F4B99020 v3
PID-7068-SETTINGS v1
557