Section 15
Logic
15.1.6
404

Operation principle

The duration of the trip output signal is settable (tTripMin). The pulse length should be
long enough to secure the opening of the circuit breaker.
There is a single input (TRINP_3P) through which all trip output signals from the
protection functions within the IED or from external protection functions via one or
more of the IEDs' binary inputs are routed. It has a single three-phase trip output
(TRIP) to connect to one or more of the IEDs' binary outputs, as well as to other
functions within the IED requiring this signal.
1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
M12255-3 v12