1MRK 511 408-UUS A
14.3
14.3.1
14.3.2
14.3.3
Phasor measurement unit RES670 2.2 ANSI
Technical manual
The following table shows the relationship between IPOS1/IPOS2 inputs and the name
of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1
IPOS2
0
0
1
0
0
1
1
1
Generic communication function for Double Point
indication DPGAPC
Identification
Function description
Generic communication function for
Double Point indication
Functionality
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indications to other systems, equipment or
functions in the substation through IEC 61850-8-1 or other communication protocols.
It is especially intended to be used in the interlocking station-wide logics.
Function block
IEC13000081 V1 EN-US
Figure 138:
DPGAPC function block
Name of displayed string Default string value
PosUndefined
Position1
Position2
PosBadState
IEC 61850
IEC 60617
identification
identification
DPGAPC
-
Section 14
Control
P00
P01
P10
P11
SEMOD55384-1 v4
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
ANSI/IEEE C37.2
device number
-
SEMOD55850-5 v7
SEMOD54710-4 v5
389