Communication Ports - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
19.7.16.2
19.8
19.8.1
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Test mode
Blocking of monitoring direction
Disturbance data
Private data
Generic services

Communication ports

The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP and
LON communication. This module is a mezzanine module, and is placed assembled on
the Numerical module (NUM). The serial communication module can have connectors
for two plastic fibre cables (snap-in) or two glass fibre cables (ST, bayonet) or a
combination of plastic and glass fibre. Three different types are available depending on
type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out, pay
special attention to the instructions concerning the handling and connection of the
optical fibres. The module is identified with a number on the label on the module.
MULTICMDRCV and MULTICMDSND
Function description
Multiple command and receive
Multiple command and send
Functionality
The IED provides two function blocks enabling several IEDs to send and receive
signals via the interbay bus. The sending function block, MULTICMDSND, takes 16
binary inputs. LON enables these to be transmitted to the equivalent receiving function
block, MULTICMDRCV, which has 16 binary outputs.
Station communication
Supported
No
Yes
Yes
Yes
No
IEC 61850
IEC 60617
identification
identification
MULTICMDRCV
-
MULTICMDSND
-
Section 19
M11874-626 v3
SEMOD119881-1 v3
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3
ANSI/IEEE C37.2
device number
-
-
M14790-3 v5
719