Technical Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
8.7.8
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Technical data

Table 147:
GOPPDOP (32) technical data
Function
Power level
for Step 1 and Step 2
Characteristic angle
for Step 1 and Step 2
Trip time, pickup at 0.5 x S
to 2 x S
r
k = 0.000
Reset time, pickup at 2 x S
r
k = 0.000
Independent time delay to trip for Step 1 and
Step 2 at 0.5 x S
to 2 x S
and
n
n
Range or value
(0.0–500.0)% of SBase
(-180.0–180.0) degrees
and
Min. =10 ms
r
Max. = 25 ms
to 0.5 x S
and
Min. = 35 ms
r
Max. = 55 ms
(0.01-6000.00) s
k = 0.000
Section 8
Current protection
SEMOD175160-1 v1
SEMOD175159-2 v9
Accuracy
±1.0% of S
at S ≤ S
n
n
±1.0% of S at S > S
n
±2.0 degrees
±0.2% or ±40 ms
whichever is greater
269

Advertisement

Table of Contents
loading

Table of Contents