ABB RES670 Technical Manual page 739

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
ComAlrmResDel
5 - 10000
RedChSwTime
0 - 500
RedChRturnTime
5 - 500
AsymDelay
-20.00 - 20.00
AnalogLatency
2 - 20
remAinLatency
2 - 20
MaxTransmDelay
0 - 40
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
MaxtDiffLevel
200 - 2000
DeadbandtDiff
200 - 1000
Table 564:
LDCMRecBinStat3 Non group settings (basic)
Name
Values (Range)
ChannelMode
Blocked
Normal
OutOfService
TerminalNo
0 - 255
RemoteTermNo
0 - 255
DiffSync
Echo
GPS
GPSSyncErr
Block
Echo
CommSync
Slave
Master
OptoPower
LowPower
HighPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel
ComAlarmDel
5 - 10000
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
ms
5
100
ms
5
0
ms
5
100
ms
0.01
0.00
-
1
2
-
1
2
ms
1
20
-
-
0-25kA
us
1
600
us
1
300
Unit
Step
Default
-
-
Normal
-
1
0
-
1
0
-
-
Echo
-
-
Block
-
-
Slave
-
-
LowPower
-
-
CT-GRP1
ms
5
100
Section 20
Remote communication
Description
Reset delay before communication alarm
signal is reset
Time delay before switching in redundant
channel
Time delay before switching back from
redundant channel
Asymmetric delay when communication use
echo synch.
Latency between local analogue data and
transmitted
Analog latency of remote terminal
Max allowed transmission delay
Compression range
Maximum time diff for ECHO back-up
Deadband for t Diff
Description
Channel mode of LDCM
Terminal number used for line differential
communication
Terminal number on remote terminal
Diff Synchronization mode of LDCM
Operation mode when GPS synchroniation
signal is lost
Com Synchronization mode of LDCM
Transmission power for LDCM
Summation mode for transmitted current
values
Time delay before communication alarm
signal is activated