ABB RES670 Technical Manual page 519

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Y
Value Reported
(1st)
(*)Set value for t: XDbRepInt
IEC05000500 V2 EN-US
Figure 198:
Periodic reporting
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Value Reported
Y2
Y1
t (*)
Magnitude dead-band supervision
If a measuring value is changed, compared to the last reported value, and the change is
larger than the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the
measuring channel reports the new value to a higher level. This limits the information
flow to a minimum necessary. Figure
band supervision. The picture is simplified: the process is not continuous but the values
are evaluated with a time interval of one execution cycle from each other.
Value Reported
Y3
Y4
t (*)
t (*)
199
shows an example with the magnitude dead-
Section 16
Monitoring
Value Reported
Value Reported
Y5
t (*)
IEC05000500-2-en.vsdx
SEMOD54417-158 v3
t
SEMOD54417-163 v6