Monitored Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
PCrv1
0.000 - 3.000
CrvSat1
0 - 100
tReset2
0.000 - 60.000
ResetTypeCrv2
Instantaneous
Frozen timer
Linearly decreased
tIReset2
0.000 - 60.000
ACrv2
0.005 - 200.000
BCrv2
0.50 - 100.00
CCrv2
0.0 - 1.0
DCrv2
0.000 - 60.000
PCrv2
0.000 - 3.000
CrvSat2
0 - 100
Table 152:
UV2PTUV (27) Non group settings (basic)
Name
Values (Range)
ConnType
PhN DFT
PhPh RMS
PhN RMS
PhPh DFT
GlobalBaseSel
1 - 12
9.1.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
-
0.001
%
1
s
0.001
-
-
s
0.001
-
0.001
-
0.01
-
0.1
-
0.001
-
0.001
%
1
Unit
Step
-
-
-
1

Monitored data

Table 153:
UV2PTUV (27) Monitored data
Name
Type
VA
REAL
VB
REAL
VC
REAL
Default
Description
1.000
Parameter P for customer programmable
curve for step 1
0
Tuning param for prog. under voltage
Inverse-Time curve, step 1
0.025
Reset time delay used in IEC Definite Time
curve step 2
Instantaneous
Selection of Time Delay reset curve for step 2
0.025
Time delay in Inverse-Time reset (s), step 2
1.000
Parameter A for customer programmable
curve for step 2
1.00
Parameter B for customer programmable
curve for step 2
0.0
Parameter C for customer programmable
curve for step 2
0.000
Parameter D for customer programmable
curve for step 2
1.000
Parameter P for customer programmable
curve for step 2
0
Tuning param for prog. under voltage
Inverse-Time curve, step 2
Default
Description
PhN DFT
Group selector for connection type
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
kV
-
kV
-
kV
Section 9
Voltage protection
PID-3586-MONITOREDDATA v6
Description
Voltage in phase A
Voltage in phase B
Voltage in phase C
275

Advertisement

Table of Contents
loading

Table of Contents