Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 8
Current protection
8.3.5
Table 108:
NS4PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
EnDir
Disable
Enable
AngleRCA
-180 - 180
VPolMin
1 - 100
I2>Dir
1 - 100
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-1>
1 - 2500
t1
0.000 - 60.000
TD1
0.05 - 999.00
IMin1
1.00 - 10000.00
t1Min
0.000 - 60.000
MultPU1
1.0 - 10.0
Table continues on next page
216

Settings

Unit
Step
-
-
-
-
Deg
1
%VB
1
%IB
1
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1.00
s
0.001
-
0.1
Default
Description
Disabled
Operation Disabled/Enabled
Enable
Enabling the Directional calculation
65
Relay characteristic angle (RCA)
5
Minimum voltage level for polarization in % of
VBase
10
Residual current level in % of IBase for
Direction release
Non-directional
Directional mode of step 1 (Disabled, Nondir,
Forward, Reverse)
ANSI Def. Time
Time delay characteristic for step 1
100
Negative sequence current op level for step 1
in % of IBase
0.000
Time delay of step 1 when definite time char.
is selected
0.05
Time multiplier for the step 1 selected time
characteristic
100.00
Minimum current for step 1
0.000
Minimum operate time for inverse time
characteristic step 1
2.0
Multiplier for scaling the current setting value
for step 1
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-4151-SETTINGS v4
Technical manual