Functionality - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
14.2.2
14.2.3
14.2.4
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Functionality

The Selector mini switch (VSGAPC) function block is a multipurpose function used
for a variety of applications, as a general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on the single line diagram
(SLD) on the local HMI or from Binary inputs
Function block
VSGAPC
BLOCK
BLOCKED
PSTO
POSITION
IPOS1
POS1
IPOS2
POS2
CMDPOS12
CMDPOS21
IEC14000066-1-en.vsd
IEC14000066 V1 EN-US
Figure 137:
VSGAPC function block
Signals
Table 215:
VSGAPC Input signals
Name
Type
BLOCK
BOOLEAN
PSTO
INTEGER
IPOS1
BOOLEAN
IPOS2
BOOLEAN
Table 216:
VSGAPC Output signals
Name
Type
BLOCKED
BOOLEAN
POSITION
INTEGER
POS1
BOOLEAN
POS2
BOOLEAN
CMDPOS12
BOOLEAN
CMDPOS21
BOOLEAN
Default
Description
0
Block of function
0
Operator place selection
0
Position 1 indicating input
0
Position 2 indicating input
Description
The function is active but the functionality is blocked
Position indication, integer
Position 1 indication, logical signal
Position 2 indication, logical signal
Execute command from position 1 to position 2
Execute command from position 2 to position 1
Section 14
Control
SEMOD158756-5 v9
SEMOD158768-4 v3
PID-6504-INPUTSIGNALS v6
PID-6504-OUTPUTSIGNALS v6
387

Advertisement

Table of Contents
loading

Table of Contents