ABB RES670 Technical Manual page 337

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
EnBlkLowI_UC1
Disabled
Enabled
BlkLowCurr_UC1
0 - 150
PickupCurr_UC1
2.0 - 150.0
tDef_UC1
0.00 - 6000.00
tResetDef_UC1
0.00 - 6000.00
HarmRestr_UC1
Disabled
Enabled
Operation_UC2
Disabled
Enabled
EnBlkLowI_UC2
Disabled
Enabled
BlkLowCurr_UC2
0 - 150
PickupCurr_UC2
2.0 - 150.0
tDef_UC2
0.00 - 6000.00
HarmRestr_UC2
Disabled
Enabled
Operation_OV1
Disabled
Enabled
PickupVolt_OV1
2.0 - 200.0
CurveType_OV1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
tDef_OV1
0.00 - 6000.00
tMin_OV1
0.00 - 6000.00
TD_OV1
0.05 - 999.00
Operation_OV2
Disabled
Enabled
PickupVolt_OV2
2.0 - 200.0
CurveType_OV2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
tDef_OV2
0.00 - 6000.00
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
-
Disabled
%IB
1
20
%IB
1.0
70.0
s
0.01
0.50
s
0.01
0.00
-
-
Disabled
-
-
Disabled
-
-
Disabled
%IB
1
20
%IB
1.0
70.0
s
0.01
0.50
-
-
Disabled
-
-
Disabled
%VB
0.1
150.0
-
-
Definite time
s
0.01
1.00
s
0.01
0.05
-
0.01
0.30
-
-
Disabled
%VB
0.1
150.0
-
-
Definite time
s
0.01
1.00
Section 11
Multipurpose protection
Description
Enable internal low current level blocking for
UC1
Internal low current blocking level for UC1 in
% of IBase
Operate undercurrent level for UC1 in % of
IBase
Definite time delay of UC1
Reset time delay used in IEC Definite Time
curve UC1
Enable block of UC1 by 2nd harmonic
restrain
Disable/Enable operation of UC2
Enable internal low current level blocking for
UC2
Internal low current blocking level for UC2 in
% of IBase
Operate undercurrent level for UC2 in % of
IBase
Definite time delay of UC2
Enable block of UC2 by 2nd harmonic
restrain
Disable/Enable operation of OV1
Operate voltage level for OV1 in % of VBase
Selection of time delay curve type for OV1
Operate time delay in sec for definite time use
of OV1
Minimum operate time for Inverse-Time
curves for OV1
Time multiplier for the dependent time delay
for OV1
Disable/Enable operation of OV2
Operate voltage level for OV2 in % of VBase
Selection of time delay curve type for OV2
Operate time delay in sec for definite time use
of OV2
331

Advertisement

Table of Contents
loading

Table of Contents