the measured quantity. Filtering is performed in accordance with the following
recursive formula:
= ×
+
-
×
X
k X
(1
k
)
X
Old
EQUATION1407 V1 EN-US
where:
X
is a new measured value (that is P, Q, S, V, I or PF) to be given out from the function
X
is the measured value given from the measurement function in previous execution cycle
Old
X
is the new calculated value in the present execution cycle
Calculated
k
is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.
Zero point clamping
In order to avoid erroneous measurements when either current or voltage signal is not
present, it is possible for the end user to set the magnitudeIGenZeroDb level for current
and voltage measurement VGenZeroDb is forced to zero. When either current or
voltage measurement is forced to zero automatically the measured values for power (P,
Q and S) and power factor are forced to zero as well. Since the measurement
supervision functionality, included in CVMMXN, is using these values the zero
clamping will influence the subsequent supervision (observe the possibility to do zero
point clamping within measurement supervision, see section
supervision").
Compensation facility
In order to compensate for small magnitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it is
possible to perform on site calibration of the power measurement. This is achieved by
setting the complex constant which is then internally used within the function to
multiply the calculated complex apparent power S. This constant is set as magnitude
(setting parameter PowMagFact, default value 1.000) and angle (setting parameter
PowAngComp, default value 0.0 degrees). Default values for these two parameters are
done in such way that they do not influence internally calculated value (complex
constant has default value 1). In this way calibration, for specific operating range (for
example, around rated power) can be done at site. However, to perform this calibration
it is necessary to have an external power meter with high accuracy class available.
Calculated
1MRK 511 408-UUS A
"Measurement
Phasor measurement unit RES670 2.2 ANSI
Technical manual
(Equation 86)
SEMOD54417-250 v5
SEMOD54417-253 v5