Section 15
Logic
416
STARTCOMB
To make it possible to provide the directional information from a protection function, a
STARTCOMB block is used in between the application function and the Start Matrix
function.
The STARTCOMB function has one block input and 14 Boolean inputs that convert
the 14 Boolean inputs into a WORD output CND, see Figure 153.
STDIRX =[ b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14 ]
b0=
START (start)
b1=
FW (forward)
b2=
REV (reverse)
b3=
STL1 (startL1)
b4=
FWL1 (forwardL1)
b5=
REVL1 (reverseL1)
b6=
STL2 (startL2)
b7=
FWL2 (forwardL2)
b8=
REVL2 (reverseL2)
b9=
STL3 (startL3)
b10=
FWL3 (forwardL3)
b11=
REVL3 (reverseL3)
b12=
STN (startN)
b13=
FWN (forwardN)
b14=
REVN (reverseN)
STARTCOMB
BLOCK
CND
BFI_3P
FW
REV
BFI_A
FW_A
REV_A
BFI_B
FW_B
REV_B
BFI_C
FW_C
REV_C
STN
FWN
REVN
ANSI16000166-2-en.vsdx
ANSI16000166 V2 EN-US
Figure 153:
STARTCOMB
1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual