ABB RES670 Technical Manual page 72

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 3
Analog inputs
Table 18:
TRM_9I_3U Non group settings (basic)
Name
Values (Range)
CT_WyePoint1
FromObject
ToObject
CTsec1
1 - 10
CTprim1
1 - 99999
CT_WyePoint2
FromObject
ToObject
CTsec2
1 - 10
CTprim2
1 - 99999
CT_WyePoint3
FromObject
ToObject
CTsec3
1 - 10
CTprim3
1 - 99999
CT_WyePoint4
FromObject
ToObject
CTsec4
1 - 10
CTprim4
1 - 99999
CT_WyePoint5
FromObject
ToObject
CTsec5
CTprim5
CT_WyePoint6
CTsec6
CTprim6
CT_WyePoint7
CTsec7
CTprim7
CT_WyePoint8
CTsec8
CTprim8
CT_WyePoint9
CTsec9
CTprim9
VTsec10
VTprim10
Table continues on next page
66
Unit
-
A
A
-
A
A
-
A
A
-
A
A
-
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
0.001 - 999.999
V
0.05 - 2000.00
kV
Step
Default
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
0.001
110.000
0.05
400.00
1MRK 511 408-UUS A
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Rated VT secondary voltage
Rated VT primary voltage
Phasor measurement unit RES670 2.2 ANSI
Technical manual
PID-3924-SETTINGS v7