Technical Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 19
Station communication
Name
Values (Range)
RemModControl
Disabled
Maintenance
All levels
AllowSimulation
No
Yes
RemSetControlEd2
Disabled
Enabled
ResvTmsEd2
1 - 3600
19.4.4
19.4.5
19.4.5.1
628
Unit
Step
-
-
-
-
-
-
s
1

Technical data

Table 470:
Communication protocols
Function
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Generic communication function for Single Point indication
SPGAPC, SP16GAPC
Functionality
Generic communication function for Single Point indication (SPGAPC) is used to send
one single logical signal to other systems or equipment in the substation.
Default
Description
Disabled
Remote Mode Control
No
Allow simulated GOOSE values or simulated
sampled measured values
Disabled
Changing settings over 61850 enabled (only
for IEC61850 Ed2)
60
Reservation time (only for IEC61850 Ed2)
Value
IEC 61850-8-1
100BASE-FX
IEC 60870–5–103
9600 or 19200 Bd
DNP3.0
300–115200 Bd
TCP/IP, Ethernet
100 Mbit/s
LON
1.25 Mbit/s
SPA
300–38400 Bd
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
IP14434-1 v1
M15031-1 v8
SEMOD55999-1 v4
SEMOD55713-5 v8
Technical manual