ABB RES670 Technical Manual page 349

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
OC1 Stage Pickup Level
PickupCurr_OC1
VDepFact_OC1 * PickupCurr_OC1
ANSI05000324 V1 EN-US
Figure 116:
Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Slope mode of operation
Voltage controlled overcurrent (when setting parameter VDepMode_OC1=Step)
OC1 Stage Pickup Level
PickupCurr_OC1
VDepFact_OC1 *
PickupCurr_OC1
ANSI05000323 V1 EN-US
Figure 117:
Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Step mode of operation
This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will as
well affect the pickup current value for calculation of trip times for IDMT curves
(overcurrent with IDMT curve will trip faster during low voltage conditions).
VLowLimit_OC1
VHighLimit_OC1
VHighLimit_OC1