ABB RES670 Technical Manual page 203

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
tPCrv3
0.005 - 3.000
tACrv3
0.005 - 200.000
tBCrv3
0.00 - 20.00
tCCrv3
0.1 - 10.0
tPRCrv3
0.005 - 3.000
tTRCrv3
0.005 - 100.000
tCRCrv3
0.1 - 10.0
IN4>Min
1 - 2500
IN4>Max
1 - 2500
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
tReset4
0.000 - 60.000
tPCrv4
0.005 - 3.000
tACrv4
0.005 - 200.000
tBCrv4
0.00 - 20.00
tCCrv4
0.1 - 10.0
tPRCrv4
0.005 - 3.000
tTRCrv4
0.005 - 100.000
tCRCrv4
0.1 - 10.0
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
%IB
1
1
%IB
1
2500
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
Current protection
Description
Param P for customized inverse trip time
curve for step 3
Param A for customized inverse trip time
curve for step 3
Param B for customized inverse trip time
curve for step 3
Param C for customized inverse trip time
curve for step 3
Param PR for customized inverse reset time
curve for step 3
Param TR for customized inverse reset time
curve for step 3
Param CR for customized inverse reset time
curve for step 3
Minimum used operate residual current level
for step 4 in % of IBase, if IN4> is less than
IN4>Min then IN4> is set to IN4>Min
Maximum used operate residual current level
for step 4 in % of IBase, if IN4> is greater
than IN4>Max then IN4> is set to IN4>Max
Reset curve type for step4 (Instantaneous /
IEC / ANSI)
Reset time delay for step 4
Param P for customized inverse trip time
curve for step 4
Param A for customized inverse trip time
curve for step 4
Param B for customized inverse trip time
curve for step 4
Param C for customized inverse trip time
curve for step 4
Param PR for customized inverse reset time
curve for step 4
Param TR for customized inverse reset time
curve for step 4
Param CR for customized inverse reset time
curve for step 4
Section 8
197

Advertisement

Table of Contents
loading

Table of Contents