Section 16
Monitoring
Name
Values (Range)
I1AngDbRepInt
1 - 100000
I2DbRepInt
1 - 100000
I2ZeroDb
0 - 100000
I2Min
0.0 - 500.0
I2Max
0.0 - 500.0
I2RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I2LimHys
0.000 - 100.000
I2AngDbRepInt
1 - 100000
Table 382:
CMSQI Non group settings (advanced)
Name
Values (Range)
3I0HiHiLim
0.0 - 500.0
3I0HiLim
0.0 - 500.0
3I0LowLim
0.0 - 500.0
3I0LowLowLim
0.0 - 500.0
I1HiHiLim
0.0 - 500.0
I1HiLim
0.0 - 500.0
I1LowLim
0.0 - 500.0
I1LowLowLim
0.0 - 500.0
I1LimHys
0.000 - 100.000
I2HiHiLim
0.0 - 500.0
I2HiLim
0.0 - 500.0
I2LowLim
0.0 - 500.0
I2LowLowLim
0.0 - 500.0
504
Unit
Step
Default
s
1
10
Type
1
10
m%
500
1000
%IB
0.1
50.0
%IB
0.1
200.0
-
-
Cyclic
%
0.001
5.000
s
1
10
Unit
Step
Default
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
%
0.001
5.000
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
1MRK 511 408-UUS A
Description
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Hysteresis value in % of range, common for
all limits
Cyclic report interval (s)
Description
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range, common for
all limits
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Phasor measurement unit RES670 2.2 ANSI