Section 23
IED hardware
23.2.7.6
818

Technical data

Table 640:
BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be activated simultaneously
with influencing factors within nominal range.
Table 641:
BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Debounce filter
Rated value
16
24/30 V
48/60 V
125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20 ms
Rated value
16
24/30 V
48/60 V
125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
SEMOD55338-1 v1
M12576-1 v9
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
M50609-2 v7
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-