Section 16
Monitoring
16.2.5
Table 401:
SSIMG Group settings (basic)
Name
Values (Range)
Operation
Off
On
PresAlmLimit
1.00 - 100.00
PresLOLimit
1.00 - 100.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tPressureAlarm
0.000 - 60.000
tPressureLO
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetPresAlm
0.000 - 60.000
tResetPresLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
526
Table 400:
SSIMG Output signals
Name
Type
LOCKOUT
BOOLEAN
PRESLO
BOOLEAN
TEMPLO
BOOLEAN
ALARM
BOOLEAN
PRESALM
BOOLEAN
TEMPALM
BOOLEAN
PRESSURE
REAL
TEMP
REAL

Settings

Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
Description
Pressure below lockout level or temperature above
lockout level
Pressure below lockout level
Temperature above lockout level
Pressure below alarm level or temperature above
alarm level
Pressure below alarm level
Temperature above alarm level
Pressure service value
Temperature of the insulation medium
Default
Description
Off
Operation Off / On
5.00
Alarm setting for pressure
3.00
Pressure lockout setting
30.00
Temperature alarm level setting of the
medium
30.00
Temperature lockout level of the medium
0.000
Time delay for pressure alarm
0.000
Time delay for pressure lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for pressure alarm
0.000
Reset time delay for pressure lockout
0.000
Reset time delay for temperture lockout
0.000
Reset time delay for temperture alarm
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6950-OUTPUTSIGNALS v6
PID-6950-SETTINGS v6