1MRK 511 408-UUS A
18.4.2
Table 463:
MU1 Non group settings (basic)
Name
Values (Range)
SampleValueID
0 - 34
APConnection
None
AP1
AP2
AP3
AP4
Table 464:
MU1_HW Non group settings (basic)
Name
Values (Range)
CTStarPoint1
FromObject
ToObject
CTStarPoint2
FromObject
ToObject
CTStarPoint3
FromObject
ToObject
CTStarPoint4
FromObject
ToObject
18.4.3
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Settings

Unit
Step
-
1
-
-
Unit
Step
-
-
-
-
-
-
-
-
Monitored data
Table 465:
MU1_HW Monitored data
Name
Type
MUDATA
BOOLEAN
SYNCH
BOOLEAN
SMPLLOST
BOOLEAN
MUSYNCH
BOOLEAN
Table continues on next page
Default
Description
ABB_MU0101
Sample Value ID (SVID) for the merging unit
[0-34 char]
None
Access point connection for the merging unit
Default
Description
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
Values (Range)
Unit
0=Ok
-
1=Error
0=Ok
-
1=Error
1=Yes
-
0=No
0=Ok
-
1=Error
Section 18
Ethernet
PID-6770-SETTINGS v2
PID-6850-SETTINGS v3
PID-6850-MONITOREDDATA v3
Description
Fatal error, data not received,
transmission errors, time-
sync issues or inconsistent
sample rate
Operational mode on
ethernet link
Fatal error or recovery state
after fatal error. High if any
subscribed channel has bad
quality or TEST while IED not
in test mode.
MU not synced or MU clock
not synced to same clock as
IED
617