Section 16
Monitoring
Name
Values (Range)
V2RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
V2LimHys
0.000 - 100.000
V2AngDbRepInt
1 - 100000
UAmpPreComp5
-10.000 - 10.000
UAmpPreComp30
-10.000 - 10.000
UAmpPreComp100
-10.000 - 10.000
Table 384:
VMSQI Non group settings (advanced)
Name
Values (Range)
3V0HiHiLim
0.0 - 200.0
3V0HiLim
0.0 - 200.0
3V0LowLim
0.0 - 200.0
3V0LowLowLim
0.0 - 200.0
V1HiHiLim
0.0 - 200.0
V1HiLim
0.0 - 200.0
V1LowLim
0.0 - 200.0
V1LowLowLim
0.0 - 200.0
V2HiHiLim
0.0 - 200.0
V2HiLim
0.0 - 200.0
V2LowLim
0.0 - 200.0
V2LowLowLim
0.0 - 200.0
Table 385:
VNMMXU Non group settings (basic)
Name
Values (Range)
VA_DbRepInt
1 - 100000
Operation
Disabled
Enabled
VA_ZeroDb
0 - 100000
Table continues on next page
506
Unit
Step
Default
-
-
Cyclic
%
0.001
5.000
s
1
10
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
Unit
Step
Default
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
Unit
Step
Default
Type
1
10
-
-
Disabled
m%
500
1000
1MRK 511 408-UUS A
Description
Reporting type
Hysteresis value in % of range, common for
all limits
Cyclic report interval (s)
Amplitude factor to pre-calibrate voltage at
5% of Vr
Amplitude factor to pre-calibrate voltage at
30% of Vr
Amplitude factor to pre-calibrate voltage at
100% of Vr
Description
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Description
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Disbled/Enabled operation
Magnitude zero point clamping in 0,001% of
range
Phasor measurement unit RES670 2.2 ANSI
Technical manual
PID-6737-SETTINGS v2